Health alert classifications

NCX Infra Controller (NICo) currently uses and recognizes the following set of health alert classifications by convention:

PreventAllocations

Hosts with this classification can not be used by tenants as instances. An instance creation request using the hosts Machine ID will fail, unless the targeted instance creation feature is used.

PreventHostStateChanges

Hosts with this classification won't move between certain states during the hosts lifecycle. The classification is mostly used to prevent a host from moving between states while it is uncertain whether all necessary configurations have been applied.

SuppressExternalAlerting

Hosts with this classification will not be taken into account when calculating site-wide fleet-health. This is achieved by metrics/alerting queries ignoring the amount of hosts with this classification while doing the calculation of 1 - (hosts with alerts / total amount of hosts).

ExcludeFromStateMachineSla

Hosts with this classification will not be counted towards state machine transition time SLA. This classification is mostly used to prevent state machine keep alerting when some manual operations are being performed on the machine.

StopRebootForAutomaticRecoveryFromStateMachine

For hosts with this classification, the NICo state machine will not automatically execute certain recovery actions (like reboots). The classification can be used to prevent NICo from interacting with hosts while datacenter operators manually perform certain actions.

Hardware

Indicates a hardware-related issue and is used as a broad bucket for hardware/BMC alerts.

SensorWarning

Indicates that a sensor reading violated a caution/warning threshold. In carbide-hardware-health, this corresponds to crossing lower_caution/upper_caution thresholds.

SensorCritical

Indicates that a sensor reading violated a critical threshold. In carbide-hardware-health, this corresponds to crossing lower_critical/upper_critical thresholds.

SensorFailure

Indicates that a sensor reading is outside the advertised valid range. In carbide-hardware-health, this corresponds to values outside range_min/range_max when that range is well-formed.

For BmcSensor alerts, severity is evaluated in this order: SensorFailure -> SensorCritical -> SensorWarning.

Special case for sensor classifications: if thresholds indicate warning/critical/failure but the BMC explicitly reports sensor health as Ok, the probe is treated as success and no alert classification is emitted.