CPU Power Telemetry

Host-side CPU power collection for NVIDIA Grace nodes, run alongside GPU DCGM power telemetry as an independent, best-effort leg.

Table of Contents


Overview

CPU power collection is a scrape-based, head-node-orchestrated design, not an in-job daemon per node writing its own files. On each worker node, srtctl launches a small HTTP exporter process directly on the bare host (outside the model container, so it can read host power interfaces) that serves a Prometheus /metrics endpoint. A single collector thread on the head node (CpuPowerCollector, src/srtctl/core/power/cpu_session.py) polls every worker's exporter on a fixed interval, parses the scrape body, and appends rows to one shared cpu/samples.csv for the whole run.

The leg is fully decoupled from the GPU DCGM power pipeline's lifecycle and is always best-effort: an unresolvable node, an unreachable exporter, a malformed scrape, or a wedged collector thread is absorbed and logged, never raised into the benchmark. There is no required flag for CPU power — gaps in samples.csv are the visible cost of a failure, not a blocked run.

Enabling It

Presence of telemetry.cpu_power_exporter (not a separate enabled flag) turns CPU power collection on:

telemetry:
  enabled: true                # master switch; also gates GPU DCGM power telemetry
  cpu_power_exporter:
    port: 9405                 # default; exporter listen port / collector scrape port
    source: auto                # "auto" | "acpi" | "dcgm", passed to the exporter binary

telemetry.enabled: true no longer requires dcgm_exporter — a recipe may configure cpu_power_exporter alone with no DCGM leg at all. The sampling cadence and timeouts (collect_interval_ms, request_timeout_seconds, startup_timeout_seconds, collector_join_timeout_seconds) are shared with the DCGM leg on TelemetryConfig; there is no separate CPU-specific set.

Config lives in CpuPowerExporterConfig (src/srtctl/core/schema.py), nested under TelemetryConfig.cpu_power_exporter. Port-collision validation (against dcgm_exporter, observability.tachometer's exporters, and any Dynamo system port) happens in SrtConfig._validate_cpu_power_exporter.

How It Starts

start_cpu_power_telemetry() in src/srtctl/cli/mixins/telemetry_stage.py is called from the sweep startup path alongside the tachometer and GPU DCGM exporter. It resolves the exporter binary, then launches one srun task per worker node (or per het-group chunk, use_bash_wrapper=False — bare host, no container):

srun --nodes=<N> --ntasks=<N> --nodelist=<nodes> \
     --output=<log_dir>/telemetry_cpu_power_exporter.%N.out \
     [--het-group=<id>] \
     <cpu-power-exporter binary> --port 9405 --source auto

The binary is resolved via _resolve_bundled_binary("cpu-power-exporter") — a Rust binary installed by make setup. When that binary is absent or not executable, srtctl falls back to a Python stdlib exporter (python3 -m srtctl.core.cpu_power_exporter), which is ACPI-only and has no --source flag; a non-auto source request logs a warning in that case instead of being silently dropped.

Once the exporter tasks are launched, CpuPowerCollector.start() resolves each worker's IP (get_hostname_ip, respecting runtime.network_interface), opens the cpu/samples.csv writer, and starts a background thread that polls every endpoint's /metrics every collect_interval_ms and appends parsed rows. Any launch failure for the exporter tasks themselves is caught and logged; the collector object is still returned (with whatever endpoints did resolve) so the caller doesn't have to special-case a partial launch.

At job teardown, stop_and_finalize() stops the collector thread, closes the CSV writer, and writes cpu_manifest.json (non-authoritative: per-node scrape/error counts and the resolved source mode, for debugging — the CSV is the source of truth).

Collection Sources

The exporter binary itself decides ACPI vs. DCGM per its own --source flag:

  • acpi — reads Linux ACPI power_meter hwmon sysfs channels. The driver name can be on the hwmon node or under device/: acpi_power_meter used hwmon_device_register() through Linux v6.14, which creates no name on the hwmon class node; v6.15 moved to hwmon_device_register_with_info(). Reports per-channel detail: cpu_rail, soc, dram, and (where firmware exposes it) a total-kind rail per socket. Domain names vary by platform (e.g. "Grace Power Socket 0" vs. a generic "Total Power socket 0", some suffixed with "in uW"); the exporter classifies all known variants into these kinds.
  • dcgm — reads the DCGM CPU-entity power fields. DCGM has no CPU power backend of its own: its sysmon module reads the same ACPI hwmon channels by power1_oem_info label, so each field is one ACPI rail:
DCGM field hwmon label it reads srtctl rail CSV column
1130 DCGM_FI_DEV_CPU_POWER_WATTS CPU Power Socket N cpu_rail power_w and cpu_rail_w
1132 DCGM_FI_DEV_SYSIO_POWER_UTIL_CURRENT SysIO Power Socket N soc soc_w
1131 DCGM_FI_DEV_CPU_POWER_LIMIT_WATTS Grace Power Socket N (cap only) — —
1133 DCGM_FI_DEV_MODULE_POWER_UTIL_CURRENT Module Power Socket N — (unverified; excluded) —

No DCGM field reports the Grace Power Socket N envelope's draw. Field 1133 does read a usage file, but what "Module" spans on GB200/GB300 (Grace alone, or the Grace+Blackwell superchip) has not been measured on a live node; it is excluded until dcgmi dmon -e 1130,1131,1132,1133 -i cpu:0 alongside cat /sys/class/hwmon/*/device/power1_oem_info settles it. So DCGM-mode power_w is the CPU rail, roughly half of ACPI-mode power_w (about 53 W vs 100 W per socket on GB200 reference runs). The energy report attaches a "CPU rail only" warning to DCGM-sourced runs; do not compare their CPU figures with ACPI-mode runs as like-for-like. The exporter publishes one cpu_power_dcgm_watts{socket,field_id} sample per field; the collector files 1130 as power_w (as it always has) and also as cpu_rail_w, and 1132 as soc_w. Older exporter builds publish 1130 alone without a field_id label; the collector treats those samples as 1130. Source: NVIDIA/DCGM modules/sysmon/DcgmSystemMonitor.cpp (label → file map) and modules/sysmon/DcgmModuleSysmon.cpp (field id → getter). - auto (default) — walks a fixed ladder at startup, most informative source first, and each source must prove itself before it is used. Every step down is logged at WARN in the exporter's .out file with the reason:

  1. ACPI, live — power_meter hwmon sensors were discovered and at least one socket-total channel (Grace Power Socket N / Total Power socket N) reads a positive value. Discovery alone is not enough: a node can expose channels that never report, and publishing them would integrate to 0 J and pass for a measurement. Only the total counts because it is what becomes power_w; a live component rail next to a dead envelope would otherwise vouch for a socket whose power can never be published. If no total reads positive, the probe is repeated once after 1 s (hwmon averages can read 0 on the first poll after boot) before ACPI is declared dead.
  2. DCGM, fields 1130 + 1132 — CPU rail and SysIO.
  3. DCGM, field 1130 alone — when this libdcgm refuses 1132 for CPU entities (older release, or a sysmon without SysIO). 1130 alone is the floor every earlier exporter had; in auto DCGM is the last resort, so failing here would mean no CPU power at all.

    Either DCGM rung is accepted only if at least one CPU entity then returns a positive field 1130 on a first read — that is the value filed as power_w. SysIO alone does not make DCGM usable: a node where only 1132 reads would publish soc_w for the whole run with no power_w and no socket rows. An all-None read usually means the embedded daemon lacks hardware access (running without root while a system dcgm-exporter holds the session). 4. Exit non-zero — no source could be established.

--source acpi and --source dcgm run only their own rungs (ACPI still requires the liveness probe to pass; DCGM still tries 1130+1132 then 1130) and exit non-zero instead of stepping down. The Python host collector (srtctl.core.cpu_power) implements the same ladder.

The exporter resolves this once at process startup and serves only one base metric family (cpu_power_dcgm_watts or cpu_power_acpi_watts) for its lifetime. Client-side parsing (src/srtctl/core/power/cpu_parser.py) prefers ACPI readings if a scrape body ever contained both, since ACPI carries more detail.

In both modes the exporter also serves superchip module power from NVML:

cpu_power_nvml_watts{type="module",socket="0",gpus="0,1",source="nvml"} 498.720000

The reading is NVML field 185 (NVML_FI_DEV_POWER_AVERAGE, a 1 s average) at NVML_POWER_SCOPE_MODULE, the value nvidia-smi prints as module.power.draw.average. The instant field is not read, so the series never mixes averaging windows. NVIDIA's Grace Performance Tuning Guide, Power and Thermals lists "Module Power" for the Grace Hopper and Grace Blackwell superchips as "Total power of the CG1 module, including DRAM power and regulator loss. This also includes GPU and GPU HBM Power", reported through nvidia-smi from release 570. CG1 names the one-GPU Grace Hopper module. The page does not say what the meter covers on a two-GPU GB200 module, so that part is measured below. On GB200 each GPU of a module reports the whole module, not its own share:

module_w = Grace + GPU_a + GPU_b + the rest of the module

The exporter therefore publishes the mean of a socket's GPU readings, one sample per socket. To avoid hiding disagreement in that mean, it withholds a socket when its GPU readings differ by more than 5% of their mean. It warns once when that starts and logs recovery at INFO when they agree again.

NVML initialization and reads run in a background thread, so blocked NVML calls do not delay the HTTP server. The module series is omitted until a reading is ready; snapshots older than 3 s are withheld. An independent timer warns once if initialization takes longer than 3 s or readings become missing or stale, and logs recovery at INFO when fresh readings return. These messages do not depend on scrapes.

Measured on a GB200 node (driver 580.126.20, kernel 6.8.0-1046-nvidia-64k) with an FMA kernel drawing about 400 W per loaded GPU, sampling nvidia-smi --query-gpu=power.draw.average,module.power.draw.average and the ACPI Grace Power Socket 0 meter together at 1 Hz, 30 to 35 samples per row:

Load GPU0 / GPU1 power.draw (W) GPU0 / GPU1 module.power.draw (W) Grace socket 0 (W)
idle 204 / 198 539 / 534 96
GPU0 only 390 / 202 731 / 725 98
GPU0 + GPU1 397 / 400 938 / 933 101

With only GPU0 loaded, GPU1's own module reading rose 191 W while its chip reading did not move, and the gap between the two module readings stayed at 6 W, the same as at idle. A meter reporting each GPU's share would have left GPU1's reading at idle. The two readings of one module differed by at most 1.1% in a steady phase and 1.9% while load fell. The residual module - Grace - GPU_a - GPU_b held at 38 to 42 W per socket under every load. The page's regulator-loss and HBM terms are candidates for it, but the probe did not attribute it.

GPUs are mapped to sockets by the NUMA node of their PCI device, taken as the ACPI socket number. On GB200 that was tested by loading the CPUs of one NUMA node at a time: NUMA node 1 (CPUs 72 to 143) raised CPU Power Socket 1 from 41 W to 203 W and left socket 0 flat, and NUMA node 0 did the reverse. GPUs 0 and 1 sit on NUMA node 0, GPUs 2 and 3 on node 1. GB300 is unverified. The collector writes module_w only onto a socket row the CPU family produced, so the exporter warns once at startup for a module socket with no CPU socket.

The series is best-effort. When NVML is unavailable the exporter logs the reason at INFO and omits the series; module_w stays blank. The aarch64 release binary links glibc so it can load libnvidia-ml, built against a glibc 2.17 floor so it runs on any aarch64 glibc; a static musl build reports Dynamic loading not supported and never serves the series. NVML is the only source of module_w. A firmware Module Power Socket N ACPI meter stays unclassified. A scrape that carries only the NVML series has no socket power and writes no rows.

Output Format

samples.csv under <log_dir>/<telemetry.storage_subdir>/cpu/ holds one row per socket per scrape. Schema v3 has header:

schema_version, timestamp_unix, hostname, source, sensor, socket_id, power_w, cpu_rail_w, soc_w, dram_w, module_w, total_power_w
  • power_w: the socket primary reading. ACPI uses the total envelope; DCGM uses field 1130, the CPU rail. A socket without its primary reading gets no row.
  • cpu_rail_w, soc_w, dram_w: component rails, blank when absent. ACPI fills those its firmware exposes; DCGM fills cpu_rail_w (= power_w, field 1130) and soc_w (field 1132). Zero or non-finite readings are missing, never interpreted as idle power. Component rails never substitute for power_w or add to total_power_w.
  • total_power_w: the sum of power_w across the node's sockets, repeated on each socket row. ACPI totals measure the socket envelope; DCGM totals sum CPU rails and are not directly comparable. Hardware traces show the total rail at roughly 93-104W against cpu_rail+soc combined at roughly 53-58W for the same socket. total measures the whole Grace SoC power boundary, not literally cpu_rail + soc.
  • module_w: superchip module power from NVML, a superset of power_w. It covers Grace, its GPUs and the rest of the module, and is never summed into total_power_w. Consumers that want the whole superchip use module_w and must not add GPU power on top, because the GPUs are already inside it. It is blank when no module reading arrived. The row's source and sensor columns describe power_w. module_w always comes from cpu_power_nvml_watts.

v1 wrote one row per rail with no rail columns. v2 pivoted to one row per socket. v3 appended module_w. Readers accept all three.

cpu_manifest.json alongside it is non-authoritative debugging metadata: per-node scrape/error counts and the resolved source mode, plus start/stop timestamps and the producer's git commit.

Computing Total Energy Over a Run

The collector intentionally never integrates power into energy — same philosophy as the GPU power artifact contract (src/srtctl/core/power/contract.py: it never integrates power into energy; that belongs to consumers of the artifact contract). To get run-total energy:

import pandas as pd
import numpy as np

df = pd.read_csv("samples.csv")
df = df[df["total_power_w"] != ""]  # skip scrapes without a node total

# total_power_w repeats across every socket row for the same (hostname, timestamp);
# dedupe before integrating or sockets get double-counted.
per_node_ts = (
    df[["hostname", "timestamp_unix", "total_power_w"]]
    .drop_duplicates(subset=["hostname", "timestamp_unix"])
    .sort_values(["hostname", "timestamp_unix"])
)

def energy_joules(group: pd.DataFrame) -> float:
    return float(np.trapezoid(group["total_power_w"].astype(float), x=group["timestamp_unix"]))

energy_per_node_j = per_node_ts.groupby("hostname").apply(energy_joules)
run_total_wh = energy_per_node_j.sum() / 3600

Use trapezoidal integration (np.trapezoid; np.trapz was removed in numpy 2.0), not mean(power) * duration — the scrape loop is not perfectly uniform, and scrape failures leave gaps. For per-socket energy instead of per-node, group by (hostname, socket_id) on power_w instead of total_power_w. Superchip energy integrates module_w the same way. Do not add GPU energy to it.

Relationship to GPU Power Telemetry

GPU power telemetry (start_gpu_power_telemetry, same mixin) works similarly in shape — an exporter process per worker node scraped by a head-node collector — but the exporter is a containerized DCGM exporter sidecar (telemetry.dcgm_exporter, launched via _start_exporter_container) rather than a bare-host process, and it is not best-effort by default: telemetry.required (which applies to the DCGM leg) can fail the benchmark stage if publishable GPU power artifacts can't be produced. CPU power has no equivalent required semantics; it is always best-effort.

GPU power limits (apply/restore audited caps, src/srtctl/core/gpu_power_limit.py) are a separate, unrelated top-level config (gpu_power_limits) — not part of telemetry.cpu_power_exporter.

Alternative: Host-Side Python Collector

telemetry.cpu_power is a second, independent CPU power leg that predates the scraper design. Instead of an exporter plus a head-node poller, srtctl launches python3 -m srtctl.core.cpu_power directly on the bare host of every worker node. Each collector reads Linux ACPI power_meter hwmon channels (or DCGM CPU entity fields 1130 and 1132) itself, writes its own per-node CSV under <storage_subdir>/nodes/, and drops a ready marker. Its --source auto walks the same ladder as the exporter (ACPI only if some sensor reads positive, then DCGM 1130+1132, then 1130 alone), logging each step down to the collector's .out file; the per-node *.metadata.json records which DCGM power fields were actually watched (power_fields[].watched). At teardown the head node (CpuPowerTelemetrySession, src/srtctl/core/cpu_power_session.py) merges the node CSVs into <storage_subdir>/samples.csv and writes manifest.json.

telemetry:
  enabled: true
  cpu_power:
    enabled: true              # presence alone is not enough; this flag turns the leg on
    source: auto               # "auto" (live ACPI, then DCGM 1130+1132, then 1130) | "acpi" | "dcgm" (mandatory)
    sample_interval_seconds: 0.1
    startup_timeout_seconds: 30.0
    required: false            # true fails the job if the leg is not ready or not publishable
    storage_subdir: cpu_power  # must differ from telemetry.storage_subdir

Differences from cpu_power_exporter:

  • Fail-closed is available. required: true blocks the formal benchmark when collectors do not become ready on every node, and turns an unpublishable result into a nonzero exit code. The scraper leg has no equivalent.
  • No network hop. Readings never leave the node until aggregation, so there is no port to reserve and no exporter binary to install.
  • Separate artifacts. Output lands in cpu_power/ by default, with an extra timestamp_local column, not in power/cpu/. The energy report (python -m srtctl.analysis.power_energy_report <log_dir>) discovers either location; when a run has both, pass --cpu-samples <path> to pick one.
  • Per-socket utilization (DCGM source only). Alongside the power fields the DCGM reader watches CPU entity fields 1100-1104 and appends five columns to every sample row: cpu_util_total, cpu_util_user, cpu_util_nice, cpu_util_sys, cpu_util_irq, reported by DCGM as a fraction of the socket's CPU time. ACPI has no utilization, so those cells stay blank. The per-node *.metadata.json lists the field ids and unit. This bumped the samples schema to v3; v2 readers that select columns by name are unaffected.

The energy report summarizes utilization per concurrency window as a mean and max of the samples inside the window, per socket and per node (and for the GPU leg's gpu_util_pct/sm_active, per GPU, node, and role). It is reported next to the joules, never integrated, and a window with no utilization samples is a warning rather than an error. Note that sm_active is only populated when the DCGM exporter is configured to emit DCGM_FI_PROF_SM_ACTIVE; the default counter set does not include it.

Each window also carries perf/W and a timing comparison:

  • perf_per_watt: output and total tokens/s over the computed window, GPU average watts and CPU+GPU combined average watts (joules / duration), and the four ratios tokens/s per watt. These are the reciprocal of the J/token figures and are computed from the same window. The combined variants are null, with a warning, unless both a CPU and a GPU leg produced samples, so they never silently equal the GPU-only number.
  • timing.computed: the window the report integrates over (aiperf: earliest request start to latest request end across profiling records; sa-bench: its wall-clock start/end). timing.reported: the benchmark's own account, for comparison only, never validation -- sa-bench's duration, aiperf's aggregate benchmark_duration/start_time/end_time, or, failing that, the profiling-phase NOTICE lines in benchmark.out when exactly one phase ran (time-of-day only, so no absolute start/end). timing.coverage: the first and last power samples the trapezoid actually spanned. Every breakdown row records its own sample_start_unix/sample_end_unix/samples.
  • Power statistics per breakdown row (socket, GPU, node, role): avg_power_w is time-weighted (joules / window duration) and therefore consistent with the energy figure even under uneven sampling; mean_w is the plain sample mean over the same samples, kept alongside so any gap between the two is visible. min_w, p5_w, p50_w, p95_w, p99_w, and max_w are sample-based percentiles (numpy linear interpolation) over the exact samples the trapezoid spanned; samples says how many points they rest on. Node and role rows are computed over the summed series, so a node p99 is the 99th percentile of the node's total power, not a sum of per-device percentiles. The text table shows p50/p95/p99/max; JSON has all.

The two legs may be enabled together. They share no ports or directories and neither one's failure affects the other.