electrical-connection-points#
Code |
EL.004 |
|---|---|
Validator |
|
Compatibility |
|
Tags |
Summary#
Equipment with electrical connections must have at least one connection point prim matching the *_electrical_nominal_voltage_* pattern.
Description#
This is a cross-domain check that reads aif:core:assetClass from the metadata domain and verifies that an electrical connection point prim exists in the geometry domain. CDUs, CRAHs, and UPS units all have AC power connections that must be represented as locatable geometry.
Why is it required?#
Ensures electrical interfaces declared in metadata are spatially represented
Simulation runtimes use CP geometry to locate power connection points for electrical simulation
Complements TC.002 (thermal piping CPs) with the electrical counterpart
Applies to#
Equipment with aif:core:assetClass = CDU, CRAH, or UPS.
Examples#
def Scope "ConnectionPoints" {
def Mesh "trane_electrical_nominal_voltage_main" { ... }
}
How to comply#
Ensure your ConnectionPoints scope contains at least one prim with electrical_nominal_voltage in its name, following the CP.004 naming convention: <vendor>_electrical_nominal_voltage[_<suffix>].