power-rating-required#
Code |
EL.002 |
|---|---|
Validator |
|
Compatibility |
|
Tags |
Summary#
AC-powered equipment must declare its power rating. The attribute name varies by equipment class.
Description#
Power rating is the primary load specification used by data center power capacity planning tools. The attribute name differs across equipment classes. See the note below.
Why is it required?#
Required for power capacity planning and load balancing in facility models
Used by electrical simulation runtimes to model power draw
Together with EL.001 (voltage) and EL.003 (frequency), fully characterizes the AC electrical input
Attribute Mapping#
Equipment Class |
Attribute |
|---|---|
CDU |
|
CRAH |
|
UPS |
|
Applies to#
Equipment with aif:core:assetClass = CDU, CRAH, or UPS.
Note on naming inconsistency#
The UPS uses upsRating (rated kVA/kW output capacity) rather than an input power rating, reflecting the different role of UPS in the power chain.
Examples#
# CDU
def Xform "CW375" {
float aif:spec:powerRating = 15.0
}
# CRAH
def Xform "CRAH500" {
float aif:spec:electricalPowerRating = 12.0
}
# UPS
def Xform "UPS5000" {
float aif:spec:upsRating = 500.0
}
How to comply#
Set the appropriate attribute for your equipment class on the default prim of the *Properties.usda sublayer, using the value from the equipment datasheet in kW (or kVA for UPS upsRating).