Feature: FET203_AIF#
Property |
Value |
|---|---|
Feature Name |
|
Runtime |
|
Proprietary Techs |
|
Latest Version |
|
Description#
Declares what a piece of equipment draws from the facility supply. An asset that satisfies this feature states its nominal voltage, power rating and line frequency, and carries an electrical connection point, so a facility power model can size a feed and detect an overload from the asset’s own declared values.
The three AC concepts appear under a different aif:spec:* name on each equipment class.
The name each class uses, and whether the class takes an AC supply at all, are declared per
class in config/aif-equipment-<class>.json rather than in the validator. The feature
applies to CDU, CRAH and UPS today. Compute rack equipment takes DC power profiles
rather than AC parameters, so the feature does not apply to it.
Dependency Graph#
flowchart LR
FET203["FET203_AIF\n0.1.0"]
FET201["FET201_AIF\n0.1.0"]
FET200["FET200_AIF\n0.1.0"]
FET203 --> FET201
FET201 --> FET200
classDef current fill:#90EE90,stroke:#333
classDef other fill:#fff,stroke:#333
class FET203 current
class FET200,FET201 other
Use Cases#
Products or workflows that consume this feature:
StratumSim datacenter physical simulation, for facility power topology and overload detection.
DSX / AI Factory operational twin, for electrical capacity planning.
Cadence and ETAP, as independent software vendors consuming the simulation data.
Power equipment manufacturers publishing datacenter assets: Vertiv, Eaton, Schneider.
Requirements#
Version 0.1.0#
Details
Used in Profiles#
This version is used in the following profiles:
AIF-Entity(v0.1.0).
Feature Dependencies#
Property |
Value |
|---|---|
Dependency |
Connection Points ( |
Requirement List#
Capability: AIF/Electrical
Requirement |
Requirement Doc |
Rule |
|---|---|---|
|
||
|
||
|
||
|
EL.004 identifies connection points by prim name under the v0.1.0 vocabulary. Under
v0.2.0 the same connections are found by querying simready:connectionPoint:domain.
Version 0.2.0#
Details
Identical requirements to v0.1.0, rebased onto the v0.2.0 Connection Points vocabulary. A v0.2.0 profile selects this version so that only one version of Connection Points is pulled into the evaluation.
Used in Profiles#
This version is used in the following profiles:
AIF-Entity(v0.2.0).
Feature Dependencies#
Property |
Value |
|---|---|
Dependency |
Connection Points ( |
Requirement List#
Capability: AIF/Electrical
| EL.001 | Nominal-Voltage-Required | Implementation |
| EL.002 | Power-Rating-Required | Implementation |
| EL.003 | Electrical-Frequency-Required | Implementation |
| EL.004 | Electrical-Connection-Points | Implementation |
Pipelines#
Source file type:
.usd,.usda,.usdcVia the AIF pipeline samples, which convert vendor CAD to USD and author the metadata.
Validation or runtime pipeline:
simready-validate— checks the electrical contract against theAIF-Entityprofile.StratumSim — consumes the declared values in a facility power model.
Samples#
Sample assets carrying electrical connection points, under sample_content/aif/:
Synthetic_UPS— UPS, nominal voltage feedSynthetic_CRAH— CRAH, fan supplyGeneric_CDU— CDU, pump supplygb300— compute rack, eight feeds
Benchmarks#
None registered. The electrical benchmark is specified on the Connection Points capability, which owns the connection vocabulary this feature layers on.
Adapters#
None.